title: Emerson UPS: Status
agents: snmp
catalog: hw/power/emerson
license: GPLv2
distribution: check_mk
description:
 This check monitors the status OID of Emerson UPS devices which have the emerson energy
 systems power MIB. They must have a system desciption OID
 starting with "Emerson Network Power".
 In case the device does not have a system description OID, it needs to be listed in
 the configuration variable {snmp_without_sys_descr} to be inventorized.

 The following states of the device are known and lead to a nagios
 state of {crit}:

 (5) "minor - MA"

 (6) "major"

 (10) "disabled"

 The following device states are known and lead to the nagios state {warn}:

 (1) "unknown"

 (3) "observation"

 (4) "warning - A3"

 (7) "unmanaged"

 (8) "restricted""

 (9) "testing"


discovery:
 One service is created for each host.