title: APC Devices: Humidity
agents: snmp
catalog: hw/environment/apc
license: GPLv2
distribution: check_mk
description:
 This check monitors the humidity of sensors attached
 to several APC devices.

 You can configure lower and upper levels for {CRIT} and {WARN}
 (default: {WARN}: 40, 60 {CRIT}: 35, 65)

 The service goes {WARN} or {CRIT} if the humidity in percent is higher
 than given upper levels or lower than the given lower levels.
 Otherwise it returns {OK}.

 This check uses the PowerNet-MIB.

item:
 The item is the sensor description of the sensor as string.

discovery:
 One service is created for each available humidity sensor.